A frame that sways carries its vertical loads with an extra lever arm, so the moments grow beyond what a first-order analysis finds. EN 1993-1-1 says when that matters (§5.2), how to include the out-of-plumbness and bow that every real frame has (§5.3), and what the member checks of §6.3 still have to cover.

Published
By
Struct4U
Reading time
7 min read
Contents

What second-order effects are

A first-order analysis calculates the internal forces on the undeformed structure. In reality the structure deflects, and the vertical loads then act on a displaced geometry: a column that leans over by δ carries its axial force N with an extra moment N · δ. That moment increases the deflection, which increases the moment again. In a stiff frame this converges quickly and the effect is small. In a flexible frame it does not, and at the elastic critical load the frame buckles.

There are two levels. Global effects (P-Δ) come from the sway of the frame as a whole; member effects (P-δ) come from the bending of each member between its ends. Both come from axial compression acting on a deformed shape, and both start from an imperfect one.

When a first-order analysis is enough: αcr

Clause 5.2.1(3) allows a first-order analysis when the deformations do not increase the internal forces significantly. That may be assumed when:

EN 1993-1-1 §5.2.1(3)
αcr= Fcr / FEd ≥ 10 for elastic analysis, ≥ 15 for plastic analysis(5.1)
αcr is the factor by which the design loads would have to be increased to cause elastic instability in a global mode; Fcr follows from the initial elastic stiffnesses.

For portal frames with shallow roofs and for beam-and-column plane frames in buildings, §5.2.1(4)B gives an approximation per storey:

EN 1993-1-1 §5.2.1(4)B
αcr= (HEd / VEd) · (h / δH,Ed)(5.2)
HEd: horizontal reaction at the bottom of the storey from the horizontal loads, including the equivalent forces of the imperfections. VEd: total vertical load at the bottom of the storey. h: storey height. δH,Ed: horizontal displacement of the top of the storey relative to its bottom, from a first-order analysis under those horizontal loads.

The approximation assumes a roof no steeper than 1:2 (26°) and no significant axial compression in the beams or rafters. The compression counts as significant when λ̄ ≥ 0.3 √(A fy / NEd) (5.3), with λ̄ the in-plane slenderness of the beam as if hinged at its ends. Outside that scope, αcr comes from an elastic buckling analysis of the frame.

Imperfections: sway and bow

Real frames are never perfectly plumb and real members never perfectly straight. §5.3 covers this with equivalent geometric imperfections, which also stand in for residual stresses and small eccentricities. Two kinds matter for frames (FIG. 1).

Global sway imperfection and local bow imperfectionLeft: a portal frame leaning over by the angle φ, drawn exaggerated; the lean can be replaced by horizontal forces φ times NEd at the top of each column. Right: a single member with an initial bow of amplitude e0 over its length L.NEdNEdφ NEdφhglobal: φ = φ₀ · αh · αm (5.5)NEde0Llocal: e₀ / L (Table 5.1)
FIG. 1The global sway imperfection φ of a frame and the local bow imperfection e0 of a member, drawn exaggerated. Both may be replaced by equivalent horizontal forces.EN 1993-1-1 §5.3.2

Global sway imperfection

EN 1993-1-1 §5.3.2(3)a
φ= φ0 · αh · αm(5.5)
φ0= 1/200, the basic value
αh= 2 / √h, with 2/3 ≤ αh ≤ 1.0 and h the height of the structure in metres
αm= √(0.5 (1 + 1/m))
m is the number of columns in a row, counting only the columns that carry at least 50 % of the average column load in the plane considered.

The sway may be modelled as an inclined geometry, or replaced by horizontal forces φ · NEd at the top of each column (§5.3.2(7)). It applies in every relevant horizontal direction, one direction at a time (§5.3.2(8)); in multi-storey frames the equivalent forces act at every floor and roof level (§5.3.2(9)). For building frames it may be ignored when HEd ≥ 0.15 VEd (5.7), that is, when the horizontal loads are already large compared with the vertical ones.

Local bow imperfection

The initial bow of a member, e0/L, depends on its buckling curve. The national annex may set its own values; Table 5.1 gives the recommended ones.

Bow imperfection e0/L, recommended values (Table 5.1)
Buckling curvea0abcd
Elastic analysis1/3501/3001/2501/2001/150
Plastic analysis1/3001/2501/2001/1501/100

In the global analysis of a frame that is sensitive to second-order effects, the bow has to be modelled only for compressed members with at least one moment-resisting joint and λ̄ > 0.5 √(A fy / NEd) (5.8). In all other cases the member checks of §6.3 cover it.

Three ways to deal with second-order effects

Clause 5.2.2(3) allows three routes, depending on the frame and the analysis.

  1. Everything in the global analysis. Second-order effects, the sway and the member bow imperfections are all in the model. No member buckling check to §6.3 is needed (§5.2.2(7)a); the cross-sections are checked with the forces from the analysis.
  2. Partly in the global analysis, partly in member checks. The analysis includes the global second-order effects and the sway imperfection. The members are then checked to §6.3 for what the analysis left out, using its end forces and moments, and the buckling length may be taken equal to the system length (§5.2.2(7)b).
  3. Member checks only. For basic cases: a first-order analysis without imperfections, with members checked to §6.3 using buckling lengths from the global buckling mode of the frame (§5.2.2(8)).

Route 3 is the classic hand method. Its weak point is the buckling length: in a sway frame it depends on the stiffness of the beams and joints and on the distribution of the axial forces, so it changes from one load combination to the next. Routes 1 and 2 avoid that question.

The amplification factor

For single-storey frames designed by elastic analysis there is a shortcut: §5.2.2(5)B allows the sway effects of a first-order analysis to be amplified instead of running a second-order analysis.

EN 1993-1-1 §5.2.2(5)B
multiply HEd and φ · VEd by 1 / (1 − 1/αcr), provided that αcr ≥ 3.0(5.4)

For αcr < 3.0 a more accurate second-order analysis applies. §5.2.2(6)B extends the method to multi-storey frames when all storeys have a similar distribution of vertical loads, horizontal loads and frame stiffness. FIG. 2 shows the factor.

Amplification factor for sway effects, EN 1993-1-1 (5.4)The factor 1/(1 − 1/αcr) plotted against αcr. Below αcr = 3 a more accurate second-order analysis is needed; between 3 and 10 sway effects may be amplified by the factor; from 10 (elastic analysis) or 15 (plastic analysis) first-order analysis is enough. The worked examples: αcr = 8.03 gives 1.142; αcr = 16.06 needs no amplification.0351015201.01.21.41.6αcr1 / (1 − 1/αcr)αcr = 8.03 → ×1.142αcr = 16.06: first ordersecond-orderamplify by (5.4)or second-orderfirst order, elasticanalysis (5.1)plastic: αcr ≥ 15
FIG. 2The amplification factor of (5.4) against αcr, with the limits of (5.1) and (5.4). The dots are the two cases of the worked example.EN 1993-1-1 §5.2.1, §5.2.2

Worked example: a portal frame

A single-storey frame with two columns, h = 6.0 m. Each column carries NEd = 120 kN, so VEd = 240 kN. The design wind load gives HEd = 12.0 kN at the top.

Sway imperfectionEN 1993-1-1 §5.3.2
αh= 2 / √6.0 = 0.816, between 2/3 and 1.0
αm= √(0.5 (1 + 1/2)) = 0.866
φ= 1/200 · 0.816 · 0.866 = 0.00354 = 1/283(5.5)
φ NEd= 0.00354 · 120 = 0.42 kN per column, 0.85 kN in total
HEd = 12.0 kN < 0.15 VEd = 36.0 kN, so the sway imperfection has to be included(5.7)

A first-order analysis under the wind load plus the equivalent forces, 12.85 kN in total, gives a horizontal displacement of 20 mm at the top. The roof is shallow and the compression in the rafter small, so (5.2) applies.

Is first order enough?EN 1993-1-1 §5.2.1(4)B
αcr= (12.85 / 240) · (6000 / 20) = 16.1 ≥ 10: first-order analysis is enough(5.2)

With more flexible columns, the same loads give a displacement of 40 mm.

The same frame, twice as flexibleEN 1993-1-1 §5.2.1, §5.2.2
αcr= (12.85 / 240) · (6000 / 40) = 8.03 < 10: second-order effects count(5.2)
αcr ≥ 3, so amplify by 1 / (1 − 1/8.03) = 1.142(5.4)
The wind load and the equivalent forces φ NEd are multiplied by 1.142, and the frame is checked with the resulting forces and moments.

In both cases the members are then checked to §6.3 for flexural and lateral-torsional buckling, with the end moments from the analysis. Because the analysis contains the global second-order effects and the sway imperfection, the buckling lengths may be taken equal to the system lengths.

How XFEM4U and XFrame2D handle it

In XFEM4U and XFrame2D, a Eurocode check for steel or timber always runs a geometrically non-linear (second-order) analysis, with the global sway imperfection of §5.3.2(3)a included automatically. XFEM4U applies it by shifting the node coordinates, once in the positive and once in the negative direction, so every ULS combination is calculated twice; XFrame2D applies the tilt in both directions of its plane. In both programs you enter m, the number of columns in a row, in the calculation settings.

The member bow imperfections of §5.3.2(3)b are not in the analysis. That is route 2: the members are checked to §6.3, and because the analysis contains the global second-order effects and the sway imperfection, the buckling length may be taken equal to the member length (§5.2.2(7)b). You do not have to derive buckling lengths from a buckling mode, and you do not have to classify the frame as sway or non-sway: if it is sensitive to second-order effects, that follows from the analysis.

Two limits. The second-order analysis applies to the beams; plates in XFEM4U are calculated geometrically linear. And the member checks still matter: a geometrically non-linear analysis without bow imperfections does not replace the buckling checks of §6.3.

Common mistakes

  • One direction only. The sway imperfection applies in each relevant horizontal direction, one at a time (§5.3.2(8)). A frame that is safe leaning one way may not be safe leaning the other.
  • No equivalent forces in αcr. HEd in (5.2) includes the equivalent forces of the imperfections, and δH,Ed has to come from the same loads.
  • (5.2) outside its scope. It is an approximation for shallow roofs and beams without significant compression. For other frames, αcr comes from an elastic buckling analysis.
  • System length after a first-order analysis. The shortcut of §5.2.2(7)b only holds when the analysis includes the global second-order effects and the sway imperfection.
  • Amplifying below αcr = 3. Then (5.4) no longer applies and a more accurate second-order analysis is required.
Sources
  1. EN 1993-1-1:2005, Eurocode 3: Design of steel structures, Part 1-1 (in the Netherlands NEN-EN 1993-1-1+C2:2011 with its national annex): §5.2.1, §5.2.2, §5.3.2, §5.3.4, Table 5.1, §6.3.
  2. The XFEM4U manual and the XFrame2D manual: Calculation settings, and References, Background, Buckling.